| ===== Testing Instructions ===== | ===== Testing Instructions ===== | ||
| + | |||
| + | <adm warning> | ||
| <note warning> The 3420 Testing process involves HIGH VOLTAGE, Make sure to disconnect power when handling connections, | <note warning> The 3420 Testing process involves HIGH VOLTAGE, Make sure to disconnect power when handling connections, | ||
| Line 194: | Line 196: | ||
| The Phase A, B, C Current should be approximately 5.9A | The Phase A, B, C Current should be approximately 5.9A | ||
| - | The Phase A, B, C Real Power should be approxmiately | + | The Phase A, B, C Real Power should be approxmiately |
| === Step 16 === | === Step 16 === | ||